8 – 40 Aquarea air/water heat pump – Installation manual for compact systems 03 / 2013
Commissioning
Programming
Weather compensation settings | Operating mode
³ Set the temperature shift as follows:
³ Press the SET button (> 5 seconds).
SETTING is shown on the display.
³ Press the SELECT button to select the temperature shift.
³ Use the UP or DOWN buttons to enter the required value
(-5 to +5°C).
³ 3UHVVWKH6(7EXWWRQWRFRQÀUPWKHVHWWLQJ
³ Press the CANCEL button or wait 30 seconds to close the entry.
³ Set the operating mode as follows:
³ Press the MODE button. The operating mode changes as follows
every time the button is pressed:
SDF model: Heat
Heat + Tank Tank
SDC model: Heat
Heat + Tank Tank Cool + Tank Cool
Weather compensation settings
Setting the operating mode
SET
SELECT
SETTING
OFF/ON
WATER OUTLET
TIMER OUTDOOR
ACTUAL
HEATER
SETTING
STATUS
SERVICE
DEFROST
HEAT
COOL
TANK
QUIET
HEATER
FORCE
BOOSTER
STATUS
SEARCH
CANCEL
CLOCK FORCE SERVICE
ERROR
RESET
OFF/ON QUIET HEATER
MODE CHECKTIMER
OPERATION
SET
SELECT
SETTING
OFF/ON
WATER OUTLET
TIMER OUTDOOR
ACTUAL
HEATER
SETTING
STATUS
SERVICE
DEFROST
HEAT
COOL
TANK
QUIET
HEATER
FORCE
BOOSTER
STATUS
SEARCH
CANCEL
CLOCK FORCE SERVICE
ERROR
RESET
OFF/ON QUIET HEATER
MODE CHECKTIMER
OPERATION
M
SET
SELECT
SETTING
CANCEL
MODE
out Lo Low outside temperature
out Hi High outside temperature
H
2
O Lo Water target temperature
at low outside temperature
H
2
O Lo Water target temperature
at high outside temperature
Water temperature
Outside
temperature
Value of
temperature
target value
shift