Reset to factory settings
Note
All settings are preserved in the
event of a power failure (stored
in EPROM). The weekday and
time are buffered by a battery
for roughly 36 hours, after
which they must be set again.
DEFROST
SETTING
STATUS
SERVICE
7. Duration of heating period (30 min
to 10 hours, Standard: 3 hours).
Setting the duration for heating mode
in the heating and water heating
operating mode.
DEFROST
SETTING
STATUS
SERVICE
8. Water heating duration (5 min to
1 hour 35 min, Standard: 30 min)
Setting the duration for water heating
in the heating and water heating
operating mode
9. Hot water immersion heating
function (YES / NO, Standard: NO)
DEFROST
SETTING
STATUS
SERVICE
10. Switch-on delay of the electric im-
mersion heater for hot water (20 min
to 1 hour 35 min , Standard: 1 hour)
Setting the delay period before the im-
mersion heating is switched on for the
hot-water tank if the tank temperature
is not reached
DEFROST
SETTING
STATUS
SERVICE
11. Sterilisation (YES / NO, Standard:
YES) Setting for sterilisation of the
hot water.
DEFROST
SETTING
STATUS
SERVICE
12. Day and time of sterilisation
(Standard: Monday 12:00 noon) Setting
day and time of the weekly sterilisation.
DEFROST
SETTING
STATUS
SERVICE
13. Sterilisation temperature
WRʝ6WDQGDUGʝ
Setting the temperature to be used
for sterilisation.
DEFROST
SETTING
STATUS
SERVICE
14. Sterilisation duration (5 min. to
1 hour, Standard: 10 min.) Setting
the period required to retain the tank
temperature required for sterilisation.