Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Planning
5
Correct arrangement of multiple mono-bloc devices with representation of the air ow
direction
Wrong Correct
1 Minimum distance: 100 mm
1
5.2.3.3 Securing the mono-bloc unit
The mono-bloc unit must be mounted on a at, horizontal and solid surface. Besides the weight of
the device, the weight of the water must also be taken into account. The unit is to be mounted with
four M12 anchor bolts, each having a tensile force of more than 15,000 N.
Minimum requirements for anchoring the mono-bloc unit on the ground by means of a
foundation (A and B) or directly in the oor plate (C)
All dimensions in mm
Note: Schematic figure for explanation purposes
only.
>
20
80
34
×100
800
4
3
5
2
≥ 300
200
≥
60
355
460
775
B
C
A
A Front view: Anchoring by means of foundation
1 Ground
2 Gravel lling
3 Strip foundation
4 Anchor bolts
5 Drain pipes
B Top view
C Detailed view: Anchoring in the oor plate
3 Strip foundation
4 Anchor bolts