EasyManua.ls Logo

Panasonic Aquarea WH-SXC09H3E5 - Mono-Bloc System

Panasonic Aquarea WH-SXC09H3E5
224 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
51
Aquarea air-to-water heat pumps - Planning and installation manual - 02/2022
Product Description
4
Bi-bloc systems | Aquarea HT | F Generation | Single Phase / Three Phase | Heating Only | R407C
Single phase (Power to indoor) Three phase (Power to indoor)
Kit KIT‑WHF09F3E5 KIT‑WHF12F6E5 KIT‑WHF09F3E8 KIT‑WHF12F9E8
Heating capacity / COP (A +7 °C, W 35 °C) kW / COP 9,00 / 4,64 12,00 / 4,46 9,00 / 4,64 12,00 / 4,46
Heating capacity / COP (A +7 °C, W 65 °C) kW / COP 9,00 / 2,48 12,00 / 2,41 9,00 / 2,48 12,00 / 2,41
Heating capacity / COP (A +2 °C, W 35 °C) kW / COP 9,00 / 3,45 12,00 / 3,26 9,00 / 3,45 12,00 / 3,26
Heating capacity / COP (A +2 °C, W 65 °C) kW / COP 9,00 / 2,06 10,30 / 2,01 9,00 / 2,06 10,30 / 2,01
Heating capacity / COP (A -7 °C, W 35 °C) kW / COP 9,00 / 2,74 12,00 / 2,52 9,00 / 2,74 12,00 / 2,52
Heating capacity / COP (A -7 °C, W 65 °C) kW / COP 9,00 / 1,79 9,60 / 1,77 9,00 / 1,79 9,60 / 1,77
ErP data for Space Heating
Average climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 153 / 125 150 / 125 153 / 125 150 / 125
SCOP W35 / W55 3,90 / 3,20 3,82 / 3,21 3,90 / 3,20 3,82 / 3,21
Energy class
1
W35 / W55 A++ / A++ A++ / A++ A++ / A++ A++ / A++
Warm climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 191 / 156 188 / 156 191 / 156 188 / 156
SCOP W35 / W55 4,84 / 3,97 4,77 / 3,97 4,84 / 3,97 4,77 / 3,97
Energy class
1
W35 / W55 A+++ / A+++ A+++ / A+++ A+++ / A+++ A+++ / A+++
Cold climate
Seasonalenergyefciency(ηs,h) W35 / W55 % 137 / 116 134 / 113 137 / 116 134 / 113
SCOP W35 / W55 3,50 / 2,97 3,42 / 2,90 3,50 / 2,97 3,42 / 2,90
Energy class
1
W35 / W55 A+ / A+ A+ / A+ A+ / A+ A+ / A+
Indoor unit
WH‑SHF09F3E5
WH‑SHF12F6E5 WH‑SHF09F3E8 WH‑SHF12F9E8
Sound pressure dB(A) 33 33 33 33
Dimension H x W x D mm 892 x 502 x 353 892 x 502 x 353 892 x 502 x 353 892 x 502 x 353
Net weight kg 46 47 47 48
Water pipe connector Inch R 1¼ R 1¼ R 1¼ R 1¼
A class pump
Number of speeds 7 7 7 7
Input power (Min / Max) W 38 / 100 40 / 106 38 / 100 40 / 106
Heatingwaterow(∆T=5K.35°C) L/min 25,8 34,4 25,8 34,4
Capacity of integrated electric heater kW 3 6 3 9
Recommended fuse A 30 / 30 30 / 30 30 / 16 30 / 16
Recommended cable size, supply 1 / 2 mm² 3 x 4,0 or 6,0 / 3 x 4,0 3 x 4,0 or 6,0 / 3 x 4,0 5 x 1,5 / 3 x 1,5 5 x 1,5 / 5 x 1,5
Outdoor unit WH‑UH09FE5 WH‑UH12FE5 WH‑UH09FE8 WH‑UH12FE8
Sound power
1)
dB(A)
Dimension H x W x D mm 1 340 x 900 x 320 1 340 x 900 x 320 1 340 x 900 x 320 1 340 x 900 x 320
Net weight kg 104 104 110 110
Refrigerant (R407C) / CO
2
Eq. kg / T 2,90 / 5,145 2,90 / 5,145 2,90 / 5,145 2,90 / 5,145
Pipe diameter Liquid / Gas Inch (mm) 3/8 (9,52) / 5/8 (15,88) 3/8 (9,52) / 5/8 (15,88) 3/8 (9,52) / 5/8 (15,88) 3/8 (9,52) / 5/8 (15,88)
Pipe length range m 3 ~ 30 3 ~ 30 3 ~ 30 3 ~ 30
Elevation difference (in/out) m 20 20 20 20
Pipe length for additional gas m 10 10 10 10
Additional gas amount g/m 70 70 70 70
Operation range
Outdoor ambient Heat °C -20 ~ +35 -20 ~ +35 -20 ~ +35 -20 ~ +35
Water outlet Heat °C 25 ~ 65 25 ~ 65 25 ~ 65 25 ~ 65
1 Scale from A+++ to D.
2 Sound power in accordance to 811/2013, 813/2013 and EN12102-1:2017 at +7 °C.
Note:
EER and COP calculation is based in accordance to EN14511.
4.6.3 Mono-bloc system
The mono-bloc system consists of one single unit that is installed outdoors and can be connected
directly to the heating circuit. The operation is e󰀨ected via wired remote controller inside the
building.

Table of Contents

Related product manuals