9 
Indoor CS-E12PKEW, CS-XE12PKEW CS-E15PKEW, CS-XE15PKEW 
Model 
Outdoor CU-E12PKE  CU-E15PKE 
Performance Test Condition  EUROVENT  EUROVENT 
Phase, Hz  Single, 50  Single, 50 
Power Supply 
V 230  230 
  Min. Mid. Max. Min. Mid. Max. 
kW  0.85 3.50 4.00 0.85 4.20 5.00 
BTU/h  2900 11900 13600 2900 14300 17100 
Capacity 
Kcal/h  730 3010 3440 730 3610 4300 
Running Current  A  – 3.8 –  – 5.5 – 
Input Power  W  250  850 1.12k 260 1.25k 1.55k 
Annual Consumption kWh  - 425 –  – 625 – 
W/W  3.40 4.12 3.57 3.27 3.36 3.23 
BTU/hW  11.60 14.00 12.14 11.15 11.44 11.03 
EER 
Kcal/hW  2.92 3.54 3.07 2.81 2.89 2.77 
Pdesign kW  3.5  4.2 
SEER (W/W)  6.6  5.9 
Annual 
Consumption 
kWh 186  249 
ErP 
Class   A++  A+ 
Power Factor  %  – 97 –  – 99 – 
dB-A  42 / 28 / 20  43 / 31 / 25 
Indoor Noise (H / L / QLo) 
Power Level dB  58 / –  59 / – 
dB-A  48 / –  49 / – 
Cooling 
Outdoor Noise (H / L) 
Power Level dB  63 / –  64 / – 
kW  0.85 4.00 6.00 0.85 5.30 6.80 
BTU/h  2900 13600 20500 2900 18100 23200 
Capacity 
Kcal/h  730 3440 5160 730 4560 5850 
Running Current  A  – 4.1 –  – 6.4 – 
Input Power  W  245  925 1.69k 255 1.43k 1.93k 
W/W  3.47 4.32 3.55 3.33 3.71 3.52 
BTU/hW  11.84 14.70 12.13 11.37 12.66 12.02 
COP 
Kcal/hW  2.98 3.72 3.05 2.86 3.19 3.03 
Pdesign kW  3.2  3.6 
Tbivalent °C  -10  -10 
SCOP (W/W)  4.0  3.6 
Annual 
Consumption 
kWh 1120  1400 
ErP 
Class   A+  A 
Power Factor  %  – 98 –  – 97 – 
dB-A  42 / 33 / 20  43 / 35 / 29 
Indoor Noise (H / L / QLo) 
Power Level dB  58 / –  59 / – 
dB-A  50 / –  51 / – 
Heating 
Outdoor Noise (H / L) 
Power Level dB  65 / –  66 / – 
Low Temp. : Capacity (kW) / I.Power (W) / COP  4.47 / 1.46k / 3.06  4.92 / 1.71k / 2.88 
Extr Low Temp. : Capacity (kW) / I.Power (W) / COP  3.37 / 1.47k / 2.29  4.11 / 1.72k / 2.39 
Max Current (A) / Max Input Power (W)  7.6 / 1.69k  8.8 / 1.92k 
Starting Current (A)  4.1  6.4