9.7.4. Energy Save Control
During Cooling Operation, press "Economy" button at remote control to enable Energy Saving Operation.
The air conditioner judges the stable condition, where the different between indoor suction temperature and setting temperature
is 1°C for 30 minutes and moderately shifts the set temperature in 0.5°C steps (Maximum 2°C) to control energy saving
operation.
If temperature different is out of range, energy save operation will not start.
Energy Save Operation is canceled by pressing the "Economy" button again.
Energy save control time chart
9.7.5. Dew Form Prevention Control
During cool or dry operation, if outdoor temperature is less than 30°C, and indoor fan speed is low or auto setting, indoor heat
exchanger temperature become lower, dew form prevention control start to prevent dew form at indoor discharge grill.
When indoor pipe temperature decrease, cooling capacity will be reduced.
9.7.6. Freeze Prevention Control
During Cooling or Dry operation, after compressor starts operation for 4 minutes, the outdoor unit will stop its operation if indoor
pipe temperature falls below 0ºC for 6 minutes.
After 3 minutes stops, compressor restarts operation if indoor pipe temperature is 6ºC or more.
This phenomenon is to protect the indoor heat exchanger from freezing and to prevent higher volume of refrigerant in liquid from
returning to the compressor.
9.7.7. Deice Control
During heating operation at low outdoor temperature, deice operation start timely to melt the ice formed on outdoor heat
exchanger.
During deice operation, in spite of any changes of remote control, indoor fan stop.
During deice operation, [DEFROST] is displayed at wired remote control, hot start operate after deice operation finish.
Deice operation start when accumulative heating operation time or after previous deice end reaches 45 minutes, the outdoor
fan maintains Hi status and the outdoor heat exchanger maintains -2°C for 5 minutes.
27