Cooling in operation according to Remote Control setting.
Time Delay Safety Control (3 minutes)
7 minutes Time Save Control
Anti-Freezing Control
If the temperature of the indoor heat exchanger falls
continuously below 2°C for 4 minutes or more, the
compressor turns off to protect the indoor heat exchanger
from freezing. The fan speed setting remains the same.
Compressor will restart again when the indoor heat
exchanger temperature rises to 10°C (Recovery).
3 minutes waiting of Time Delay Safety Control is valid for
Cooling Operation.
Compressor Reverse Rotation Protection Control
Anti-Dew Formation Control
7 Operation Details
7.1. Cooling Mode Operation
When the compressor is stopped by Remote Control, it restarts after 3 minutes when it is turned ON by Remote Control.
When the setting temperature is reached during cooling operation, the compressor stops and it will not start for 3 minutes.
The compressor will start automatically if it has stopped for 7 minutes even if the room temperature is between the compressor
ON temperature and OFF temperature.
If the compressor is operating continuously for 5 minutes or longer and the temperature difference between intake air and
indoor heat exchanger is 2.5°C or less for 2 minutes, compressor will stop and restart automatically.
(Time Delay Safety Control is valid)
T = Intake air temperature - Indoor heat exchanger temperature
This is to protect reverse rotation of the compressor when there is a instantaneous power failure.
Purpose is to prevent dew formation on indoor unit air discharge area.
When the following conditions occur for 30 minutes continuously, anti-dew formation is controlled by indoor fan speed shift to
low (Changed to HLo):
Indoor intake air temperature is more than 24°C and less than 30°C.
Remote Control setting temperature is less than 25°C.
Compressor is on.
Cooling operation mode.
Indoor Fan motor operate at Low fan speed.
This control is cancelled immediately when above condition is changed.
19
CS-A12CTP CU-A12CTP5 / CS-A18CTP CU-A18CTP5 / CS-A24CTP CU-A24CTP5

Other manuals for Panasonic CS-V12CTP

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic CS-V12CTP and is the answer not in the manual?

Panasonic CS-V12CTP Specifications

General IconGeneral
BrandPanasonic
ModelCS-V12CTP
CategoryAir Conditioner
LanguageEnglish

Related product manuals