Time Delay Safety Control
Anti-Freezing Control
Compressor Reverse Rotation Protection Control
Compressor Protection Control
Anti-Dew Formation Control
Automatic Fan Speed Mode
7.2. Soft Dry Mode Operation
•
The unit starts cooling operation until the room temperature reaches the setting temperature set on the Remote Control, and
then Soft Dry operation will start.
•
During Soft Dry operation, the Indoor Fan will operate at Lo- speed.
•
The operation will be switched on and off for up to 10 minutes “ON” and 6 minutes “OFF”. Once Soft Dry operation is turned
off, it stops for 6 minutes.
•
Once the compressor stops, it will not start for 3 minutes during Cooling operation.
•
Same as Anti-Freezing Control for Cooling Mode operation. (For Soft Dry region, 6 minutes waiting is valid during compressor
stops.)
•
Same as Compressor Reverse Rotation Protection Control for Cooling Mode Operation. (For Soft Dry region, 6 minutes waiting
is valid during compressor stops.)
•
Same as Compressor Protection Control for Cooling Mode Operation.
•
Same as Anti-Dew Formation Control for Cooling Mode operation.
When Automatic Fan Speed is selected at Remote Control during Soft Dry operation.
•
Fan speed rotates at Lo- speed.
22