– 25 –
MAC9702008C2
CS-MC90KE
Operation Details
5) Sleep Mode Auto Operation
Cooling or Soft Dry Operation
6) Auto Restart Control
• If there is a power failure, operation will be automatically restarted when the power is resumed.
It will start with previous operation mode and airflow direction.
(Time Delay Safety Control is valid)
• Auto Restart Control is not available when Timer or Sleep Mode is set.
• This control can be omitted by cutting the jumper wire J2. (Refer Circuit Diagram)
When you press the SLEEP Mode, the following move-
ment will start to avoid overcooling.
• The fan speed is automatically set to Low.
• The setting temperature will be risen by 0.5°C at the
start of operation and by 0.5°C one hour later.
• The operation will stop after 8 hours.
7) Indoor Fan Speed Control
• Auto Fan Speed Control
When set to Auto Fan Speed, the fan speed is adjusted between maximum and minimum setting as shown in the
table.
• Manual Fan Speed Control
Basic fan speed adjustment (3 settings, from Lo to Hi) can be carried out by using the Fan Speed selection
button.
START
STOP
1 HOUR
8 HOURS
0.5°C UP
0.5°C UP
SET
TEMP.
Fan Speed
Hi
t
t
Manual
Automatic
Cooling
Soft Dry
Air Circulation
Me
t
t
Lo
t
t
t
SLo
t
* SLo: Indoor Fan rotates at 4-second intervals at Low speed.
Stop
t
t