– 27 –
MAC9702008C2
CS-MC90KE
No.
1
2
3
4
5
Accessories part
Installation plate
Installation plate fixing screw
Remote control
Battery
Air purifying filter
MODEL
MC140K
MC180K
3MC200K
Piping size
Gas
3/8"
3/8"
3/8"
Liquid
1/4"
1/4"
1/4"
Rated
Length
10
10
10
Max.
Elevation
(m)
5
5
5
Max.
Piping
Length
(m)
15
15
15
Additional
Refrigerant
(g/m)
15
15
15
No.
6
7
8
Accessories part
Clamping cover of piping
Vinyl tape
Vinyl tape
Qty.
1
3
1
Installation Information
Attached accessories
Accessories: Flaring piping kit
CZ-3F5, 7EN
SELECT THE BEST LOCATION
• There should not be any heat source or steam near the unit.
• There should not be any obstacles blocking the air circulation.
• A place where air circulation in the room is good.
• A place where drainage can be easily done.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling, fence or other obstacles.
• Indoor unit of this room air conditioner shall be installed on the wall in a height of at least 2.3 m.
• If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the
condenser is not obstructed.
• There should not be any animal or plant which could be affected by hot air discharged.
• Keep the spaces indicated by arrows from wall, ceiling, fence or other obstacles.
• Do not place any obstacles which may cause a short circuit of the discharged air.
• If piping length is over the rated length, additional refrigerant should be added as shown in the table.