3
When Installing
Select an installation location which is rigid and strong
enough to support or hold the unit, and select a location
for easy maintenance.
In a Room
Properly insulate any tubing run inside a room to prevent
“sweating” that can cause dripping and water damage to
walls and floors.
CAUTION
Keep the fire alarm and the air outlet at least
1.5 m away from the unit.
In Moist or Uneven Locations
Use a raised concrete pad or concrete blocks to provide
a solid, level foundation for the outdoor unit. This
prevents water damage and abnormal vibration.
In an Area with High Winds
Securely anchor the outdoor unit down with bolts and a
metal frame. Provide a suitable air baffle.
In a Snowy Area (for Heat Pump-type Systems)
Install the outdoor unit on a raised platform that is higher
than drifting snow. Provide snow vents.
When Connecting Refrigerant Tubing
WARNING
When performing piping work do not
mix air except for specifIed refrigerant
(R410A) in refrigeration cycle. It
causes capacity down, and risk of
explosion and injury due to high
tension inside the refrigerant cycle.
Refrigerant gas leakage may cause
fire.
Do not add or replace refrigerant
other than specified type. It may
cause product damage, burst and
injury, etc.
Ventilate the room well, in the event that is refrigerant
gas leaks during the installation. Be careful not to allow
contact of the refrigerant gas with a flame as this will
cause the generation of poisonous gas.
Keep all tubing runs as short as possible.
Use the flare method for connecting tubing.
Apply refrigerant lubricant to the matching surfaces of
the flare and union tubes before connecting them, then
tighten the nut with a torque wrench for a leak-free
connection.
Check carefully for leaks before starting the test run.
Do not leak refrigerant while piping work for an
installation or re-installation, and while repairing
refrigeration parts.
Handle liquid refrigerant carefully as it may cause
frostbite.
When Servicing
Turn the power OFF at the main power box
(mains) before opening the unit to check or repair
electrical parts and wiring.
Keep your fingers and clothing away from any moving
parts.
Clean up the site after you finish, remembering to
check that no metal scraps or bits of wiring have been
left inside the unit being serviced.
WARNING
Do not clean inside the indoor and
outdoor units by users. Engage
authorized dealer or specialist for
cleaning.
In case of malfunction of this
appliance, do not repair by yourself.
Contact the sales dealer or service
dealer for repair.
CAUTION
Do not touch the air inlet or the
sharp aluminum fins of the
outdoor unit. You may get injured.
Ventilate any enclosed areas when
installing or testing the refrigeration
system. Escaped refrigerant gas, on
contact with fire or heat, can produce
dangerously toxic gas.
Confirm after installation that no
refrigerant gas is leaking. If the gas
comes in contact with a burning stove,
gas water heater, electric room heater
or other heat source, it can cause the
generation of poisonous gas.
Others
CAUTION
Do not touch the air inlet or
the sharp aluminum fins of the
outdoor unit. You may get injured.
Do not sit or step on the unit,
you may fall down accidentally.
Do not stick any object into
the FAN CASE.
You may be injured and the
unit may be damaged.
NOTICE
The English text is the original instructions. Other
languages are translations of the original instructions.
MiniVRFeng.indd3MiniVRFeng.indd3 2011/08/2613:45:102011/08/2613:45:10
AMP Air Conditioning
www.ampair.co.uk | sales@ampair.co.uk

Other manuals for Panasonic EAIRC-MJ Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic EAIRC-MJ Series and is the answer not in the manual?

Panasonic EAIRC-MJ Series Specifications

General IconGeneral
BrandPanasonic
ModelEAIRC-MJ Series
CategoryAir Conditioner
LanguageEnglish

Related product manuals