WR901 FP-X0
Address
Name
Description
R9010
Always on relay
Always on.
R9011
Always off relay
Always off.
R9012
Scan pulse relay
Turns on and off alternately at each scan.
R9013
Initial (on type) pulse
relay
Goes on for only the first scan after operation (RUN) has
been started, and goes off for the second and subsequent
scans.
R9014
Initial (off type) pulse
relay
Goes off for only the first scan after operation (RUN) has
been started, and goes on for the second and subsequent
scans.
R9015
Step ladder initial pulse
relay (on type)
Turns on for only the first scan of a process after the boot at
the step ladder control.
R9016
Not used
-
R9017
Not used
-
R9018 0.01 s clock pulse relay
Repeats on/off operations in 0.01
sec. cycles.
R9019 0.02 s clock pulse relay
Repeats on/off operations in 0.02 s.
cycles.
R901A 0.1 s clock pulse relay
Repeats on/off operations in 0.1 s.
cycles.
R901B 0.2 s clock pulse relay
Repeats on/off operations in 0.2 s.
cycles.
R901C 1 s clock pulse relay
Repeats on/off operations in 1 s.
cycles.
R901D 2 s clock pulse relay
Repeats on/off operations in 2 s.
cycles.
R901E 1 min clock pulse relay
Repeats on/off operations in 1 min.
cycles.
R901F