3-3
3.1.2 Power Supply Specifications
AC Power Supply
Item
Specifications
E30
Rated voltage 100 to 240 V AC
Voltage regulation range 85 to 264 V AC
Inrush current 40 A or less (at 240 V AC, 25 C)
Momentary power off time 10 ms (when using 100 V AC)
Frequency 50/60 Hz (47 to 63 Hz)
Leakage current 0.75 mA or less between input and protective earth terminals
Internal power supply part
Guaranteed life
20,000 hours (at 55 C)
Fuse Built-in (Cannot be replaced)
Insulation system Transformer insulation
Terminal screw M3
Service Power Supply for Input (Output) (AC power supply type only)
Item
Specifications
E30
Rated output voltage 24 V DC
Voltage regulation range 21.6 to 26.4 V DC
Rated output current 0.4 A
Overcurrent protection
function
Note)
Available
Terminal screw M3
Note) This is a function to protect overcurrent temporarily. If a current load that is out of the
specifications is connected, it may lead to damages.
DC Power Supply
Item
Specifications
E30
Rated voltage 24 V DC
Voltage regulation range 20.4 to 28.8 V DC
Inrush current 12 A or less (at 25 C)
Momentary power off time 10 ms
Internal power supply part
Guaranteed life
20,000 hours (at 55 C)
Fuse Built-in (Cannot be replaced)
Insulation system Transformer insulation
Terminal screw M3