FP2 Serial Data Unit
Parts and Functions
2 − 4
2.1 Parts and Functions
2.1.2 Operation Status Display LEDs
The operation status display shows status conditions such as the communication status
of the unit and errors/alarms.
Display Operation
Alarm (red)
Lighted: Unit error (Lights on watchdog timer error)
Not lighted: Goes out when there is no error
COM.1 Sent data monitoring
Blinks during sending
SD (green)
Goes out when there is no sent data
Received data monitoring
Blinks during reception
RD (green)
Goes out when there is no reception data
Communication error
Lights when communication error occurs
ERR (red)
Goes out when normal frame is received
COM.2 Sent data monitoring
Blinks during sending
SD (green)
Goes out when there is no sent data
Received data monitoring
Blinks during reception
RD (green)
Goes out when there is no reception data
Communication error
Lights when communication error occurs
ERR (red)
Goes out when normal frame is received
LED status ( :on : blink :off)
Note
The ERROR LED for communication error lights if a parity,
framing, overrun, or BCC error occurs.