16
20. INTENDED PRODUCTS FOR CE MARKING
The models listed under “19. SPECIFICATIONS” come with CE Marking.

Contact for CE
<Until June 30 ,2013>
Panasonic Electric Works Europe AG
Rudolf-Diesel-Ring 2, D-83607 Holzkirchen, Germany
<From July 1 ,2013>
Panasonic Marketing Europe GmbH Panasonic Testing Center
Winsbergring 15, 22525 Hamburg,Germany
<Conditions in use for CE marking conformity>
The harmonized standard with regard to immunity that applies to this product is EN 61000-6-2
and the following condition must be met to conform to that standard.
Be sure to meet the condition 1 and, furthermore, the condition either 2 or 3 should also be
met.
Condition
1. Cable length between the main power supply and the S-LINK controller should be under
10m.
2. When the power is supplied from S-LINK controller to I/O devices at a cable distance of
more than 10m, add a surge absorber between 24V and 0V at a cable distance of under
10m.
Recommended surge absorber: ERZ05D390 (Panasonic product)
3. Use a local power supply at a cable distance of under 10m from each I/O device.
Note: Do not connect a surge absorber between D and G.