3
No. Description Function
7
Transmission indicator
(SEND) (Green)
It blinks to indicate the synchronization signal used for signal transmission / reception.
8
Error indicators
(ER1, 3, 4) (Red × 3)
They light up according to the type of error.
(Refer to “14. ERROR INDICATORS.”)
9
S-LINK terminal block
connector
S-LINK system’s signal line and power supply are connected.
(Refer to “4. MOUNTING AND CONNECTION.”)
10
DeviceNet terminal block
connector
It is a connector for connection of DeviceNet.
(Refer to “4. MOUNTING AND CONNECTION.”)
11
DeviceNet indicators
(Green, Red)
They display the communication status of DeviceNet.
NET STATUSPOWER
MODULE STATUS
Indication Signal
NET STATUS
Green lights up Communication connection completed
Green blinks Setting incomplete
Red lights up Fatal communication error
Red blinks Small communication error
MODULE STATUS
Green lights up Normal operation
Green blinks Wait state
Red lights up Fatal error
Red blinks Small error
POWER Green lights up Power supplied
12
DeviceNet transmission
speed setting (RATE)
Transmission speed of DeviceNet is set.
Transmission speed 1 0
125kbps OFF OFF
250kbps OFF ON
500kbps ON OFF
Invalid ON ON
13
DeviceNet address
setting (MAC ID)
Address of DeviceNet is set.
MAC ID 32 16 8421
0 OFF OFF OFF OFF OFF OFF
1 OFF OFF OFF OFF OFF ON
2 OFF OFF OFF OFF ON OFF
3 OFF OFF OFF OFF ON ON
···
···
···
···
···
···
···
62 ON ON ON ON ON OFF
63 ON ON ON ON ON ON