Easy Start Guide
Page 5
This guide has been produced by The Inverter Drive Supermarket Ltd.
All content, including but not limited to graphics, text and procedures copyright The Inverter
Drive Supermarket and must not be reproduced or altered without prior written permission.
©
4. Parameters - overview
Default is 50 or 60 depending on region. Set at for 50Hz motor.50
Default is 0. Set to for most applications.0
Set to match motor nameplate - eg. 4.7
Default is 50. Change to 60 for 60Hz motor only - otherwise set at .50
See section 6 for details of how to correctly set this value.
The Inverter contains a number of settings
which can be changed to tailor it for use in a
wide range of applications. These settings are
known as parameters.
Parameters are typically referred to by code or
number (eg. P6 = Motor Full Load Current)
with a description available in the manual.
The parameters contain critical information
essential to the correct operation of the
Inverter. Therefore, they should at least be
checked by the user before it is operated for
the first time.
The parameters listed in section 5 are intended
to provide a starting point to allow for basic
operation of the 650 Inverter.
5. Parameters to set before use
See section 7 to learn how to set a parameter value.
Set the following parameters to allow the 650
to run in standard mode with Run, Stop and
Speed Control from the keypad.
If any of the parameters have been changed
previously, follow the procedure in section 13
to reset the Inverter to Factory Defaults.
5.1 Parameters to check and values to set
Parker SSD Drives 650 Series Inverter