6.2.1 Reduce motor speed to 10%.
Press the “E” (escape) key twice to return to the speed
display. Then press and hold the down key to reduce the
speed from 100% to 10%.
Once the motor is running at 10%, proceed to the next step.
6.2.3 Locate parameter P13 and change as required.
From the output current display in the previous step, press
“E” to return to “diag” then up and down to locate “par” as
shown.
Press “M” to open the parameter list then up and down to
locate P13. Press “M” again to edit it.
6.2.4 Change P13, save and check output current.
Use the up and down keys to increase or decrease the
value of P13 as necessary. Press “E” to save and “E” to
return to “par”, then “E” again to return to the speed display.
Repeat step 6.2.2 to check output current. If it matches
motor no-load current Boost is set correctly and the motor
can be stopped using the red button.
If the output current does not match, repeat steps 6.2.3 and
6.2.4 until it does.
6.2.2 Use the diagnostics menu to find output current.
Press and hold the “M” button until the display shows “diag”
as before. Press “M” again to open the diagnostics menu.
Use the up and down keys to locate output current as
before.
If the current value shown is more than motor no-load
current, the Boost value in P13 will need to be reduced. If it
is less, P13 will need to be increased.
6.2 How to use “Motor no-load current” to set Boost correctly.