EasyManua.ls Logo

Parker CDAS HL 050 - Page 26

Parker CDAS HL 050
75 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
25
Medium Flow Compressed Air Dryers - IOMI.
Remote Stop / Start Connection
CDAS HL / OFAS HL / FBP HL dryers can be congured to enable remote shut down and start up (Stop / Start) of the dryer. is
requires a 24VDC signal to be supplied to the remote stop digital input (RC) on the control board and setting of DIL Switch 8 on
Dipswitch Array 1 to enable
DIPSWITCH ARRAY (1)
DIL SWITCH FUNCTION OFF ON
8 Remote Stop / Start Remote Stop Inhibited Remote Stop Enabled
e dryer control board supplies the 24V DC required to
operate the Remote Stop / Start function.
Required for operation:
An external remote switch (latching type).
A 2 core twisted screened cable (0.75mm
2
), max length 30m.
Connect one core of the screened cable from the “+” on the
dryer control board to the remote switch via the screened
cable.
Connect the other core of the screened cable between the
remote switch and the RC connection on the control board.
Remote Stop / Start Operation
When remote stop / start has been connected and enabled using the DIL
Switch 8 on Dipswitch Array 1, an icon will be shown on the display.
When the remote switch is open, the icon will have a grey background with
a line through it and the dryer will operate normally.
When the remote switch is closed, a 24V DC signal is applied to the digital
input (RC).
e icon background will change from grey to blue and the line will
disappear to indicate that the dryer has been remotely stopped.
e dryer will continue to cycle until the end of the current half cycle then
stop.
e dryer will remain in this state until the remote switch is opened, where
the controller will re-start the drying cycle on a fully regenerated desiccant
bed.
When the dryer has been remotely "Stopped"
e fault relay(s) will remain energised
e icon on the display will change to indicate the dryer has been
remotely stopped.
Energy Saving modes "ECO" & "Purge Economy" are overridden