Control Connections for Local Control      Refer to the Installation Diagram 
  Control wiring must have a minimum cross-section area of 0.75mm
2
 (18AWG) 
  Use screened control cables to comply with EMC requirements 
 
Connection to allow the MAIN CURR. LIMIT parameter to adjust the current limit. 
Removing B8 from C9 (24V) causes a Program Stop (regenerative drive only) 
Removing B9 from C9 (24V) causes a Coast Stop 
The Emergency Stop relay (normally-open, delay on de-energisation) is not sequenced via 
the drive. It is a separate control feature. 
The contact between terminals C5 (ENABLE) and C9 must be closed for the drive to run. 
Terminals C1 and C2 must be linked for the drive to run 
(External Trip interlock not required in this simple set-up). 
Via the clean earth rail which originates directly from the main incoming earth rail.