Parker RAC Europe PSD04 | User manual ver. 3.6 | Code 144PSDI364
Page 36 of 74
Pc13 1.0 100.0 K 40.0 User PID proportional band
Pc14 0 999 s 120 User PID integral time
Pc15 0 999 s 30 User PID derivative time
Pc20 1 255 s 5 Installer start-up delay
Pc21 0.00 100.00 % 50.00 Installer start-up position
Par. Min. Max. Units Default Menu Parameters set n. 2
Pp01 3.0 25.0 K 6.0 User SH setpoint
Pp02 1.0 3.0 K 2.0 User LoSH setpoint
Pp03 10.0 40.0 K 15.0 User HiSH setpoint
Pp04 -200.0 40.0 °C -40.0 User Set2 LOP temperature
Pp05 -40.0 40.0 °C 40.0 User MOP temperature
Pp13 1.0 100.0 K 40.0 User PID proportional band
Pp14 0 999 s 120 User PID integral time
Pp15 0 999 s 30 User PID derivative time
Pp20 1 255 s 5 Installer start-up delay
Pp21 0.00 100.00 % 50.00 Installer start-uo position
Par. Min. Max. Units Default Menu Common SH algorithm
Fast 1 100 - - - - 100 User fast action
PNHi 0.0 25.0 K 1.0 User neutral high threshold
Pcz PNHi 25.0 K 3.0 User constant proportional threshold
SHFi 0 255 100 ms 10 User SH filter time constant
FaTh -10.0 10.0 K -1.0 User fast action threshold
Par. Min. Max. Units Default Menu Protections and alarms
Pa01 0 1 - - - - 0 Installer
enable communication alarm
1 = yes