Pa02 5 120 s 30 Installer communication alarm delay
Pa10 0 1 - - - - 0 Installer
enable LoSH alarm
1 = yes
Pa11 0.0 25.0 K 0.5 Installer LoSH alarm hysteresis
Pa12 0 250 min 3 Installer LoSH alarm delay
Pa20 0 1 - - - - 0 Installer
enable HiSH alarm
1 = yes
Pa21 0.0 25.0 K 1.0 Installer HiSH alarm hysteresis
Pa22 0 250 min 3 Installer HiSH alarm delay
Pa30 0 1 - - - - 0 Installer
enable low pressure alarm
1 = yes
Pa31 0.00 45.00 barG 0.00 Installer low pressure setpoint alarm
Pa32 0.20 1.00 barG 0.30 Installer low pressure alarm hysteresis
Pa33 0 250 min 3 Installer low pressure alarm delay
Pa40 0 1 - - - - 0 Installer
enable LOP alarm
1 = yes
Pa41 0.0 10.0 K 1.0 Installer LOP alarm hysteresis
Pa42 0 250 min 3 Installer LOP alarm delay
Pa50 0 1 - - - - 0 Installer
enable MOP alarm
1 = yes
Pa51 0.0 10.0 K 1.0 Installer MOP alarm hysteresis
Pa52 0 250 min 3 Installer MOP alarm delay
Pa53 0.0 25.0 K 7.0 Installer MOP maximum dSH applicable
Pa54 0.0 25.0 K 8.0 Installer MOP band
Pa55 0 255 10 s 15 Installer MOP filter time constant
Pa56 0 255 min 10 Installer MOP bypass delay