Parker RAC Europe PSD04 | User manual ver. 3.6 | Code 144PSDI364
Page 39 of 74
Pi07 1 16 - - - - 1 Manufact.
valve selection
1 = Sporlan SER AA
2 = Sporlan SER A
3 = Sporlan SER B
4 = Sporlan SER C
5 = Sporlan SER D
6 = Sporlan SERI F
7 = Sporlan SERI G
8 = Sporlan SERI J
9 = Sporlan SERI K
10 = Sporlan SERI L
11 = Sporlan SEHI 175
12 = Sporlan SEHI 400
13 = Reserved
14 = Sporlan EDEV B/C (unipolar)
15 = Reserved
16 = Reserved
Par. Min. Max. Units Default Menu Valve and driver: driver settings
Pr05 0.00 100.00 % 0.00 Installer probe alarm position
Pr06 0 9 - - - - 0 Manufact.
enabling mode
0 = from digital input DI1 or DI2
(stand alone)
1 = from digital input DIHV (stand
alone)
2 = from CANBUS
3 = reserved
4 = from serial MS RS-485
5 = reserved
6 = from CANBUS + DI1 or DI2 as
consequence of communication
error
7 = reserved
8 = from serial MS RS-485 + DI1 or
DI2 as consequence of
communication error
9 = reserved
Pr08 0 255 s 1 Installer stabilization delay
Pr09 0.00 100.00 % 50.00 Installer stabilization position
Pr20 0.00 100.00 % 0.00 Installer stand-by position
Pr30 50.00 100.00 % 100.00 Manufact. limit valve opening
Pr40 0 9999 h 0 User working hour (read only parameter)