Parker RAC Europe PSD04 | User manual ver. 3.6 | Code 144PSDI364
Page 40 of 74
Pr41 0 365 day 1 Installer
resynchronization interval
0 = disabled
Pr45 30 100 % 100 Manufact. reserved
Pr48 0.00 100.00 % 0.00 Installer communication error position
Par. Min. Max. Units Default Menu Valve and driver: debug
Prd0 25 1000 step/s 25 User debug step rate
Prd1 0.00 Prd2 % 0.00 User debug minimum position
Prd2 Prd1 100.00 % 100.00 User debug maximum position
Par. Min. Max. Units Default Menu Valve and driver: backup battery
Pb01 0 1 - - - - 0 Installer
backup battery
1 = present
Par. Min. Max. Units Default Menu
Valve and driver: digital I/O
settings and various
Ph01 0 8 - - - - 0 Manufact.
digital output DO1 function
0 = disabled
1 = any alarm
2 = probe errors
3 = following low SH alarms
4 = following MOP alarms
5 = following valve alarm
6 = used for solenoid valve
7 = alarms + used for solenoid
valve
8 = valve resyncchronization signal
is necessary
Ph02 0 1 - - - - 0 Manufact.
relay logic
0 = normally unexcited
1 = normally excited
Ph10 0 1 - - - - 0 Manufact.
free of voltage digital input DI1 logic
0 = normally open
1 = normally closed