Parker RAC Europe PSD04 | User manual ver. 3.6 | Code 144PSDI364
Page 42 of 74
Piu1 0 4 - - - - 1 Manufact.
analog input AI1 function
0 = not used
1 = suction temperature backup
probe
2 = suction pressure backup probe
Pia1 1 30 - - - - 1 Manufact.
analog input AI1 probe type
1 = NTC probe
6 = Pt 1000 probe
10 = 4-20 mA transducer (0.5 - 8
barA)
11 = 4-20 mA transducer (0 - 30
barA)
12 = 4-20 mA transducer (-1 - 8
barG)
13 = 4-20 mA transducer (-1 - 15
barG)
14 = 4-20 mA transducer (0 - 30
barG)
20 = 0-5 V (0 - 7 barG)
21 = 0-5 V (0 - 25 barG)
22 = 0-5 V (0 - 60 barG)
30 = scaling
AI1T 2 7 - - - - ??? User
AI1 type (used if Piu1 = 0)
2 = NTC
3 = 0-20 mA
4 = 4-20 mA
5 = 0-5 V
6 = reserved
7 = Pt 1000
Par. Min. Max. Units Default Menu
Probe settings: analog input AI1
scaling
P1Xty 0 2 - - - - 0 Manufact.
X type
0 = 0-20 mA
1 = 4-20 mA
2 = 0-5 V
P1XM P1Xm
0:20.00
1:20.00
2:5.00
- - - - 20.00 Manufact. X max value
P1Xm
0:0.00
1:4.00
2:0.00
P1XM - - - - 0.00 Manufact. X min value