P1Tty 0 1 - - - - 0 Manufact.
Y type
0 = barG
1 = barA
P1YM P1Ym 300.00 barG/barA 1.00 Manufact. Y max value
P1Ym
-
300.00
P1YM barG/barA 0.00 Manufact. Y min value
Par. Min. Max. Units Default Menu Probe settings: analog input AI2
Piu2 0 2 - - - - 0 Manufact.
analog input AI2 function
0 = not used
1 = suction temperature backup
probe
2 = suction pressure backup probe
Pia2 1 30 - - - - 1 Manufact.
analog input AI2 probe type
1 = NTC probe
6 = Pt 1000 probe
10 = 4-20 mA transducer (0.5 - 8
barA)
11 = 4-20 mA transducer (0 - 30
barA)
12 = 4-20 mA transducer (-1 - 8
barG)
13 = 4-20 mA transducer (-1 - 15
barG)
14 = 4-20 mA transducer (0 - 30
barG)
20 = 0-5 V (0 - 7 barG)
21 = 0-5 V (0 - 25 barG)
22 = 0-5 V (0 - 60 barG)
30 = scaling
AI2T 2 7 - - - - ??? User
AI1 type (used if Piu2 = 0)
2 = NTC
3 = 0-20 mA
4 = 4-20 mA
5 = 0-5 V
6 = reserved
7 = Pt 1000