Par. Min. Max. Units Default Menu
Probe settings: analog input AI2
scaling
P2Xty 0 2 - - - - 0 Manufact.
X type
0 = 0-20 mA
1 = 4-20 mA
2 = 0-5 V
P2XM P2Xm
0:20.00
1:20.00
2:5.00
- - - - 20.00 Manufact. X max value
P2Xm
0:0.00
1:4.00
2:0.00
P2XM - - - - 0.00 Manufact. X min value
P2Yty 0 1 - - - - 0 Manufact.
Y type
0 = barG
1 = barA
P2YM P2Ym 300.00 barG/barA 1.00 Manufact. Y max value
P2Ym
-
300.00
P2YM barG/barA 0.00 Manufact. Y min value
Par. Min. Max. Units Default Menu Probe settings: analog input AI3
Piu3 3 3 - - - - 3 Manufact.
analog input AI3 function
3 = suction temperature probe
Pia3 1 6 - - - - 1 Manufact.
analog input AI3 probe type
1 = NTC probe
6 = Pt 1000 probe
Par. Min. Max. Units Default Menu Probe settings: analog input AI4
Piu4 4 4 - - - - 4 Manufact.
analog input AI4 function
4 = suction pressure probe