Parker RAC Europe PSD04 | User manual ver. 3.6 | Code 144PSDI364
Page 45 of 74
Pia4 10 30 - - - - 10 Manufact.
analog input AI4 probe type
10 = 4-20 mA transducer (0.5 - 8
barA)
11 = 4-20 mA transducer (0 - 30
barA)
12 = 4-20 mA transducer (-1 - 8
barG)
13 = 4-20 mA transducer (-1 - 15
barG)
14 = 4-20 mA transducer (0 - 30
barG)
20 = 0-5 V (0 - 7 barG)
21 = 0-5 V (0 - 25 barG)
22 = 0-5 V (0 - 60 barG)
30 = scaling
Par. Min. Max. Units Default Menu
Probe settings: analog input AI4
scaling
P4Xty 0 3 - - - - 0 Manufact.
X type
0 = 0-20 mA
1 = 4-20 mA
2 = 0-5 V
3 = 0-10 V
P4XM P4Xm
0:20.00
1:20.00
2:5.00
3:10.00
- - - - 20.00 Manufact. X max value
P4Xm
0:0.00
1:4.00
2:0.00
3:0.00
P4XM - - - - 0.00 Manufact. X min value
P4Yty 0 1 - - - - 0 Manufact.
Y type
0 = barG
1 = barA
P4YM P4Ym 300.00 barG/barA 1.00 Manufact. Y max value
P4Ym
-
300.00
P4YM barG/barA 0.00 Manufact. Y min value
Par. Min. Max. Units Default Menu Probe settings: offset
OfsTs -10.0 10.0 K 0.0 User suction temperature offset