Parker RAC Europe PSD04 | User manual ver. 3.6 | Code 144PSDE364
page 69 of 74
The maximum lengths of the connecting cables are the following:
- power supply device: 30 m (98 ft)
- analog inputs: 100 m (328 ft)
- power supply 0-20 mA/4-20 mA/0-5 V ratiometric/0-10 V
transducers: 100 m (328 ft)
- free of voltage digital inputs: 100 m (328 ft)
- high voltage digital input: 100 m (328 ft)
- digital output: 100 m (328 ft)
- bipolar stepper motor output: 5 m (16 ft; 10 m (32 ft) with
shielded cable)
- CAN port:
- 1,000 m (3,280 ft) with baud rate
20,000 baud
- 500 m (1,640 ft) with baud rate 50,000 baud
- 250 m (820 ft) with baud rate 125,000 baud
- 50 m (164 ft) with baud rate 500,000 baud
- power supply remote user interface: 30 m (98 ft)
- RS-485 port: 1,000 m (3,280 ft); also look at the MODBUS
specifications and implementation guides manual.
Operating temperature: from -10 to 60 °C (from 14 to 140 °F).
Storage temperature: from -20 to 70 °C (from -4 to 158 °F).
Operating humidity: from 10 to 90% of relative humidity not condensing.
Pollution situation: 2.
Power supply:
24 VAC +10% -15%, 50/60 Hz ±3 Hz, 40 VA max. not isolated or
24... 37 VDC, 22 W max. not isolated, supplied by a class 2 circuit.
If the device is powered in direct current, it is necessary to respect
the polarity of the power supply voltage.
Protect the power supply with a fuse rated 2 A-T 250 V.
Overvoltage category: III.
Analog inputs:
4 inputs of which 2 inputs (non optoisolated, which can be set via
configuration parameter for NTC/Pt 1000 probes and for 0-20
mA/4-20 mA/0-5 V ratiometric transducers) which can be set via
configuration parameter for suction temperature backup
probe/suction pressure backup probe, 1 input (non optoisolated,
which can be set via configuration parameter for NTC/Pt 1000
probes) as suction temperature probe and 1 input (non
optoisolated, which can be set via configuration parameter for
0-20 mA/4-20 mA/0-5 V ratiometric/0-10 V transducers) as suction
pressure probe.