Parker RAC Europe PSD04 | User manual ver. 3.6 | Code 144PSDE364
page 70 of 74
NTC analog inputs (10K @ 25 °C, 77 °F)
Kind of sensor: ß3435.
Working range: from -40 to 110 °C (from -40 to
230 °F) for standard NTC probes
from -50 to 150 °C (from -58 to
302 °F) for high temperature NTC
probes
from -50 to 110 °C (from -58 to
230 °F) for fast NTC probes.
Accuracy: ±0.6% of the full scale for standard
and fast NTC probes
±0.5% of the full scale for high
temperature NTC probes.
Resolution: 0.1 °C (1 °F).
Conversion time: 100 ms.
Protection: none.
Pt 1000 analog inputs (1K @ 0 °C, 32 °F)
Working range: from -100 to 400 °C (from -148 to
752 °F).
Accuracy: ±0.5% of the full scale.
Resolution: 0.5 °C (1 °F).
Conversion time: 100 ms.
Protection: none.
0-20 mA/4-20 mA analog inputs
Input resistance: to 200 .
Accuracy: ±1% of the full scale.
Resolution: 0.01 mA.
Conversion time: 100 ms.
Protection: none; the maximum current
allowed on each input is 25 mA.
0-5 V ratiometric analog inputs
Input resistance: to 10K .
Accuracy: ±1% of the full scale.
Resolution: 0.01 V.
Conversion time: 100 ms.
Protection: against the reversal of polarity.
0-10 V analog inputs
Input resistance: to 10K .
Accuracy: ±1% of the full scale.
Resolution: 0.01 V.
Conversion time: 100 ms.
Protection: against the reversal of polarity.