EasyManua.ls Logo

ParTech ASLD2200 - Symptom: the Sensor Drives to the Top Limit; Fault: Sensor Is Fouled; Fault: Faulty External up Switch

Default Icon
30 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ASLD2200 - Instruction Manual
Encoder centre adjustment
Loosen 2x pozi screws on encoder bracket and slide the encoder assembly left or right until the encoder arms are
positioned centrally over the blade of the encoder disc
Encoder depth adjustment
Loosen the 2x Allen screws and adjust encoder bracket so that the encoder disc blade is positioned deep into the
encoder arms about 1mm clearance from the back.
After adjustment, check that disc blade is not touching any part of the encoder when the motor is moving.
11.2 Symptom: The sensor drives to the top limit.
11.2.1 Fault: Sensor is fouled
Clean the sensor.
If the problem persists after sensor cleaning then the sensor is likely to have failed. Contact Partech.
11.2.2 Fault: Faulty External UP Switch
Replace switch
103370IM Issue 10 Date 19/03/2018 Page 23 of 30
ENCODER ALIGNMENT
ENCODER
DISC
ENCODER
ASSEMBLY
ENCODER
ASSEMBLY
BRACKET
CENTRE
ADJUSTMENT
DEPTH
ADJUSTMENT
BELT
TENSIONER
ENCODER ALIGNMENT
ENCODER
DISC
ENCODER
ASSEMBLY
ENCODER
ASSEMBLY
BRACKET
CENTRE
ADJUSTMENT
DEPTH
ADJUSTMENT
BELT
TENSIONER