MIC 1400 Manual Edition 1
28
DISPLAY AVAILABLE FACTORY
STEP DESCRIPTION CODE SETTINGS SETTING
6 Output 2% Po2 0 to 100% Read Only
7 1st Output Pb1 0 to 999.9% 5.0
Prop. Band of Input Span
0%=On/OFF
8 2nd Output Pb2 0 to 999.9% 5.0
Prop. Band of Input Span
0%=ON/OFF
9 Automatic ArSt OFF to 99 mins. OFF
Reset 59 secs
10 Rate rAtE 0 sec to 99 mins. 0 secs.
59 secs.
11 Overlap/ SPrd -20 to 20% of 0%
Deadband Pb1 and Pb2
12 Manual Reset rSEt 0 to 100% Output 1 25%
-100 to 100% Out 2
13 Hysteresis
Output 1 HyS1 0.1 to 10.0% of span 0.5
Output 2 HyS2 0.1 to 10.0% of span 0.5
Out 1 & Out 2 HySt 0.1 to 10.0% of span 0.5
14 Setpoint SPuL Span Max. Span Max.
Upper Limit
15 Setpoint SPLL Span Min. Span Min.
Lower Limit
16 Process Pou -1999 to 9999 Span Max.
Output Upper
17 Process PoL -1999 to 9999 Span. Min.
Output Lower