ELECTRICAL DATA
OUTDOOR UNIT
UNIT V-PH-HZ
VOLTAGE RANGE COMPR FAN MOTORS POWER SUPPLY
Min Max LRA RLA
No. of
Fans
FLA
Min Ckt
Amps
MOCP
(Amps)
PH1S090
208/230-3-60 187 254 160 31.5 1 3.1 42.5 50
460-3-60 414 508 80 15.7 1 1.4 21.0 25
LEGEND
FLA Full Load Amps
LRA Locked Rotor Amps
MOCP Maximum Overcurrent Protection (Fuse Only)
RLA Rated Load Amps
INDOOR UNIT
UNIT
PF1B
V*-PH-HZ
VOLTAGE
LIMITS
FAN MOTOR POWER SUPPLY
Hp FLA
Minimum
Circuit
Amps
MOCP
(Amps)
090
208/230-1-60 187-253 2.4 11.0 13.8 20
208/230-3-60 187-253 2.4 5.8 7.3 15
460-3-60 414-528 2.4 2.6 3.3 15
LEGEND
FLA Full Load Amps
Hp Horsepower
MOCP Maximum Overcurrent Protection
*Motors are designed for satisfactory operation within 10% of nominal voltages shown.
Voltages should not exceed the limits shown in the Voltage Limits column.