ON-LINE RACK PH 9360 - PH 9301 .
3.Operations
3.1. Button Operation, Phasak UPS
Function
• Turn on the UPS: Press and hold the button more than 0.5s to turn on the UPS.
• Enter Key: Press this button to confirm the selection in setting menu.
• Turn off the UPS: Press and hold the button more than 0.5s to turn off the UPS.
• Esc key: Press this button to return to last menu in setting menu.
• Battery test: Press and hold the button more than 0.5s to test the battery while in AC
mode, or CVCF mode.
• UP key: Press this button to display next selection in setting menu.
• Mute the alarm: Press and hold the button more than 0.5s to mute the buzzer. Please
refer to section 3-4-9 for details.
• Down key: Press this button to display previous selection in setting menu.
• Press and hold the two buttons simultaneous more than 1s to enter/escape the
setting menu.
* CVCF mode means converter mode.
3.2. Acoustic Alarm, Phasak UPS
Description
Alarm Interval
Mute
State of the UPS
bypass Mode
Alarm every 2 minutes
Yes
Battery Mode
Alarm every 4 seconds
Failure
Alarm continuous
Alert
Overload
It sounds 2 times every seconds
Not
Other
Alarm times seconds
Failure
All
Alarm continuing
Yes
77 / 100