1.8.5 Connecting the Installation Local Bus
(BK Module With IP 65/IP 67 Protection)
Figure 1-26 Connecting the installation local bus
1 Cap nut
2 Compression ring
3 Grommet
4 Splice ring
• Push the cap nut (1), the compression ring (2) and the grommet (3)
onto the cable (Figure 1-26, A).
• Strip 15 mm (0.591 in.) off the outer cable sheath.
• First push the grommet to the end of the cable sheath, then push the
compression ring onto the grommet.
This provides the strain relief for the cable (Figure 1-26, B).
• Insert the wire ends into the splice ring openings (Figure 1-26, C).