Diagnostics
Getting started Modular safety relay,myPNOZ
1005615-EN-02
| 26
Module
LED
Function LED Meaning Remedy
Flashes
red
Output LED
flashes green
Error at the output
} Output LED flashes (or both LEDs
flash simultaneously)
Feedback loop is not closed
when starting or attempting to
switch on
Output is switched off, but there
is still voltage at the output
} Both LEDs flash alternately
Total current at the semicon-
ductor outputs of an I/O module
too high
Supply voltage at the semicon-
ductor output of an I/O module
too high
Total current at the semicon-
ductor outputs of an I/O module
briefly very high
Short circuit between two semi-
conductor outputs on a module
Short circuit between semicon-
ductor output and GND
Check wiring of feedback loop,
rectify error
Check wiring of output for short
circuits, rectify error
Keep within the permitted sup-
ply voltage range (see mod-
ule’s technical details)
Rectify short circuit
Rectify short circuit