PNOZ 16
Operating Manual PNOZ 16
1003517-EN-09
| 26
Conventional thermal current
while loading several contacts
774066 774067
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current with 1 con-
tact 8 A 8 A
Conv. therm. current with 2 con-
tacts 6 A 6 A
Times 774066 774067
Switch-on delay
With automatic start typ. 230 ms 230 ms
With automatic start max. 350 ms 350 ms
With automatic start after power
on typ. 310 ms 310 ms
With automatic start after power
on max. 450 ms 450 ms
With manual start typ. 230 ms 230 ms
With manual start max. 350 ms 350 ms
Delay-on de-energisation
With E-STOP typ. 18 ms 18 ms
With E-STOP max. 30 ms 30 ms
With power failure typ. 50 ms 50 ms
With power failure max. 100 ms 100 ms
Recovery time at max. switching
frequency 1/s
After E-STOP 50 ms 50 ms
After power failure 100 ms 100 ms
Supply interruption before de-ener-
gisation 20 ms 20 ms
Simultaneity, channel 1 and 2 max.
Environmental data 774066 774067
Climatic suitability EN 60068-2-78 EN 60068-2-78
Ambient temperature
Temperature range -10 - 55 °C -10 - 55 °C
Storage temperature
Temperature range -40 - 85 °C -40 - 85 °C
Climatic suitability
Humidity 93 % r. h. at 40 °C 93 % r. h. at 40 °C
Condensation during operation Not permitted Not permitted
EMC EN 60947-5-1, EN 61000-6-2, EN
61326-3-1
EN 60947-5-1, EN 61000-6-2, EN
61326-3-1
Vibration
In accordance with the standard EN 60068-2-6 EN 60068-2-6
Frequency 10 - 55 Hz 10 - 55 Hz
Amplitude 0,35 mm 0,35 mm