6 Commissioning
6.1 Generalwiringguidelines
ThewiringisdefinedinthecircuitdiagramofthePNOZmultiConfigurator.Itispossibleto
definewhichinputsandoutputsonthesafetysystemwillcommunicatewithPROFINET.
Pleasenote:
} Informationgiveninthe"Technicaldetails[ 20]"mustbefollowed.
} Usecopperwiringwithatemperaturestabilityof75°C.
PleasenotethefollowingwhenconnectingtoPROFINET:
} Thefollowingminimumrequirementsoftheconnectioncableandconnectormustbe
met:
– OnlyusestandardindustrialEthernetcableandconnectors.
– OnlyusedoubleshieldedtwistedpaircableandshieldedRJ45connectors(indus
trialconnectors).
– 100BaseTXcableinaccordancewiththeEthernetstandard(min.Category5)
} Measurestoprotectagainstinterference:
EnsuretherequirementsfortheindustrialuseofPROFINETaremet,asstatedinthe
InstallationManualpublishedbytheUserGroup.
} Externalmeasuresmustbeusedtoconnecttheterminal tothefunctionalearth,
whenthemountingrailisnotconnectedtothefunctionalearth.
} Alwaysconnectthemountingrailtotheprotectiveearthviaanearthingterminal.This
willbeusedtodissipatehazardousvoltagesinthecaseofafault.
} Thepowersupplymustmeettheregulationsforextralowvoltageswithprotectivesep
aration.
CAUTION!
Onlyconnectanddisconnecttheexpansionmodulewhenthesupply
voltageisswitchedoff.
NOTICE
Wheninstalling,youmustrefertotheguidelinespublishedbythe
RPOFIBUS&PROFINETInternational(PI)UserGroup.
6.2 Connectingthesupplyvoltage
Connectthesupplyvoltagetothefieldbusmodule:
} Terminal24V:+24VDC
} Terminal0V:0V