PSEN sl-1.0p 1.1/1.1 VA
Operating Manual PSEN sl-1.0p 1.1/1.1 VA
1003821-EN-12
13
Possible remedies:
} Set the supply voltage constantly to the upper tolerance range (see Technical details:
System with normal actuator [ 27], System with free-moving actuator [ 30],
System with normal actuator and stainless steel base plate [ 34]).
} Select a higher conductor cross section
} Reduce load at the outputs, e.g. with evaluation device PNOZe1.1p
Recommended cable cross sections
Prerequisite:
} Supply voltage: 24V
} Cable type: LiYY 8x0.25 mm² (79Ohm/km) from Pilz
Max. load per safety output 100mA 500mA
Cable length 45m 24m
If cable lengths greater than those stated in the table are required, please contact Pilz.
Pin assignment
8-pin M12 connector
PIN Function Terminal designation
Cable colour (Pilz
cable)
1 Input, channel 2 S21 White
2 +24 V UB A1 Brown
3 Safety output channel 1 12 Green
4 Safety output channel 2 22 Yellow
5 Signal output Y32 Grey
6 Input, channel 1 S11 Pink
7 0 V UB A2 Blue
8 "Lock_Unlock" S31 Red
The wire colour also applies for the cable available from Pilz as an accessory.