PZE X4.1P
Operating Manual PZE X4.1P
1003203-EN-09
| 16
Order no. 777588 – 787588
General 777588 787588
Certifications
CCC, CE, EAC (Eurasian), TÜV,
cULus Listed
CCC, CE, EAC (Eurasian), TÜV,
cULus Listed
Electrical data 777588 787588
Supply voltage
Voltage 24 - 240 V 24 - 240 V
Kind AC/DC AC/DC
Voltage tolerance -15 %/+10 % -15 %/+10 %
Output of external power supply
(AC) 4 VA 4 VA
Output of external power supply
(DC) 2 W 2 W
Frequency range AC 50 - 60 Hz 50 - 60 Hz
Residual ripple DC 20 % 20 %
Duty cycle 100 % 100 %
Inputs 777588 787588
Number 2 2
Voltage at
Input circuit DC 24 V 24 V
Current at
Input circuit DC 30 mA 30 mA
Max. overall cable resistance Rl-
max
Single-channel at UB DC 70 Ohm 70 Ohm
Single-channel at UB AC 70 Ohm 70 Ohm
Dual-channel without detection
of shorts across contacts at UB
DC 140 Ohm 140 Ohm
Dual-channel without detection
of shorts across contacts at UB
AC 140 Ohm 140 Ohm
Relay outputs 777588 787588
Number of output contacts
Safety contacts (N/O), instant-
aneous 4 4
Max. short circuit current IK 1 kA 1 kA
Utilisation category
In accordance with the standard EN 60947-4-1 EN 60947-4-1