EasyManua.ls Logo

Pilz PZE X4.1P - Technical Specifications: AC;DC Timing and Environmental; AC;DC Timing, Environmental, and Vibration Data

Pilz PZE X4.1P
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PZE X4.1P
Operating Manual PZE X4.1P
1003203-EN-09
| 18
Conventional thermal current
while loading several contacts
777588 787588
Ith per contact at UB DC;
AC1:240V,DC1:24V
Conv. therm. current with 1 con-
tact 6 A 6 A
Conv. therm. current with 2 con-
tacts 6 A 6 A
Conv. therm. current with 3 con-
tacts 4,5 A 4,5 A
Conv. therm. current with 4 con-
tacts 3,5 A 3,5 A
Times 777588 787588
Switch-on delay
With automatic start typ. 15 ms 15 ms
With automatic start max. 20 ms 20 ms
With automatic start after power
on typ. 230 ms 230 ms
With automatic start after power
on max. 360 ms 360 ms
Delay-on de-energisation
With E-STOP typ. 10 ms 10 ms
With E-STOP max. 20 ms 20 ms
With power failure typ. UB 240 V 1300 ms 1300 ms
With power failure max. UB 240
V 1900 ms 1900 ms
With power failure typ. UB 24 V 270 ms 270 ms
With power failure max. UB 24 V 350 ms 350 ms
Supply interruption before de-ener-
gisation in the input circuit 2 ms 2 ms
Supply interruption before de-ener-
gisation 20 ms 20 ms
Environmental data 777588 787588
Climatic suitability EN 60068-2-78 EN 60068-2-78
Ambient temperature
Temperature range -10 - 55 °C -10 - 55 °C
Storage temperature
Temperature range -40 - 85 °C -40 - 85 °C
Climatic suitability
Humidity 93 % r. h. at 40 °C 93 % r. h. at 40 °C
Condensation during operation Not permitted Not permitted
EMC EN 60947-5-1, EN 61000-6-2, EN
61000-6-4, EN 61326-3-1
EN 60947-5-1, EN 61000-6-2, EN
61000-6-4, EN 61326-3-1
Vibration
In accordance with the standard EN 60068-2-6 EN 60068-2-6
Frequency 10 - 55 Hz 10 - 55 Hz
Amplitude 0,35 mm 0,35 mm

Related product manuals