Installation, use and maintenance
M0097D rev.00 ENIT
¦ Dispense the fluid at the flow rate for which you require the highest
possible metering precision into a graduated container with minimum
capacity of  litres. Do not reduce the flow rate to bring the level
to the graduated area of the container; the correct technique is to
start and stop the flow repeatedly without changing the flow rate until
reaching the required filling level.
¦ Compare the indication on the graduated container (true value) with
the reading on the flow meter (indicated value):
¦ if the indicated value is higher than the true value, unscrew the
adjuster screw.
¦ if the indicated value is lower than the true value, tighten the adjuster
screw.
¦ Repeat steps from to until the level of precision is satisfactory.
Turning on the
CUBE
For all CUBE versions it is sufficient to:
¦ take the dispensing nozzle away from the rest;
¦ li the rest (ON).