28 - ATR224 - DRR224 - User manual
GROUP M -
d.i.1
- Digital input 1
231
d .i .1. f.
Digital Input 1 Function
Digital input functioning.
diS a b.
Disabled (Default)
2 t. s w.
2 Setpoints Switch
rUn
Run
tune
Performing manual tune
a u. m a .i.
Automatic / Manual Impulse (if enabled on parameter 48 or 67)
a u.m a.c.
Automatic / Manual Contact (if enabled on parameter 48 or 67)
a ct.t Y.
Action Type. Cooling regulat. if D.I. is active, otherwise heating reg.
M. reS.
Manual reset. Reset the outputs if selected as manual reset.
232
d .i .1. c.
Digital Input 1 Contact
Defines the resting contact of the digital input .
n.o pen
№rmally open (Default)
n.cLos.
№rmally closed
235÷238 Reserved Parameters - Group M
Reserved parameters - Group M
GROUP Q -
sft.s
- Soft-start and mini cycle
264
SS.TY.
Soft-Start Type
Enables and selects the soft-start type
diS a b.
Disabled (Default)
Gra d.
Gradient
P erc.
Percentage (only with pre-programmed cycle disabled)
266
SS.Gr.
Soft-Start Gradient
Rising/falling gradient for soft-start and pre-programmed cycle.
.. Digit/hour
p.
(degrees.tenths/hour if temperature). (Default: .)
267
SS.Pe.
Soft-Start Percentage
Output percentage during soft-start function.
..%. (Default: %)
268
SS. tH.
Soft-Start Threshold
Threshold under which the soft-start percentage function is activated, at starting.
-... [digit
p.
] (degrees.tenths for temp. sensors) (Default: )
269
SS.ti .
Soft-Start Time
Max. Softstart duration: if the processs will not reach the threshold selected on par. SS.tH. within
the selected time, the controller starts to regulate on setpoint.
00:00
Disabled
00:01-24:00
hh:mm (Default: 00:15)