15
1) date,
2) time,
3) measurement from 1 sensor (T1),
4) battery voltage,
5) power supply,
6) name of file
9 ALARMS
Type of alarms depends on set parameters set in application AVIA
9.1 Temperature / humidity
User will be notified in case of:
• Damage of sensor 1 or sensor 2 (indications transcend over the acceptable operating range of
sensor),
• Values from sensor 1 or 2 transcend over the acceptable operating range set in parameters-
alarms event and the time set in column ‘delay’ passed by.
• Return of the value on sensor 1 or 2 to the set temperature and acceptable range.
If the ‘delay’ is set e.g to 5 min (in case temperature will exceed), the alarm will not turn on if the
temperature value will return to acceptable range in faster than 5 minutes (see chart below).
By setting the delay properly you can prevent unnecessary alarms caused by e.g opening the
door to load the samples or defrosting function in the refrigerator.