EasyManua.ls Logo

Ponsel ACTEON 5000 - Configuring Analog Outputs

Ponsel ACTEON 5000
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
38
Version 2.1
Update: April 2016
PONSEL Mesure Aqualabo Contrôle
35 Rue Michel Marion 56850 CAUDAN, FRANCE
Tel.: +33(0)2 97 89 25 30 Fax: +33(0)2 97 76 55 72
6.2.5 Configuring the Analog outputs.
To access the "Analog output settings" window, select the icon in the Main menu.
The functionality offered for the setting up of the two analog outputs is described in the table below:
Set-up line
Functionality
MM: Err/Maintenance
mode
Used to set the Maintenance Mode to one of the following modes:
Automatic (the default option, and which is activated when the calibration
menu is used, or if there is a loss of communication, etc.)
Inactive
Manual (this mode is activated manually when maintenance or other work is
performed on the device).
State of outputs in
MM
In Maintenance Mode, the analog outputs may return a value corresponding
to:
- the last value measured,
- a fixed (unchanged) value which shall be defined in the "OUT. 1: Value mA
in MM" and "OUT. 2: Value mA in MM" lines.
OUT. 1: Value mA in
MM
This line is used to set the value which will be returned by analog output 1
when the device is in Maintenance Mode (between 0 and 21 mA).
OUT. 2: Value mA in
MM
This line is used to set the value which will be returned by analog output 2
when the device is in Maintenance Mode (between 0 and 21 mA).
MM Final tempo (mn)
Used to set a time delay which shall begin when the Maintenance is
completed, to allow a period of time for the measurement to stabilize. The
possible values are: 0 to 60 minutes (1 min is the default setting).
Configuration of the Analog Output 1
OUT1 :Active
function
Configuration of the output 1 according to 4 choices:
No function
Recorder
Test Fixed Value
PID Controler
If Active Function : Recorder
OUT 1: Active
Function
This function activates analog output 1.
Used to set output 1 to Data logger mode (for when the output is connected
to a controller/data logger).
OUT. 1: DL type
Used to set output 1 to operate within a range of 0-20 mA or 4-20 mA.
OUT. 1: Parameter
linked to DL
Used to select the parameter whose value shall be outputted via analog
output 1:
Sensor 1: Primary parameter
Sensor 1: Secondary parameter
Sensor 2: Primary parameter

Table of Contents