7. Repairs
7.2 List of faults
Code Fault Possible causes Action
P3
Water intake temperature sensor malfunction
1) Sensor badly connected 1) Reconnect sensor
2) Sensor defective 2) Replace sensor
3) PCB defective 3) Replace PCB
P4
Water outlet temperature sensor malfunction
Same causes as P3 Same actions as P3
P1
De-icing temperature sensor malfunction
P7
External temperature sensor malfunction
P2
Air venting sensor
malfunction
P8
Water temperature at outlet too low
for cooling mode
1) Water ow rate too low 1) Check water lter and hydraulic circuit
2) Water temperature at intake too low 2) Adjust temperature
3) Defective PCB 3) Replace PCB
PC
Antifreeze protection
Protection activated when the ambient temperature is
too low and the unit is on standby
No intervention is necessary
E4
High pressure protection
1) Insufcient water ow
1) Check water pump operation and openings of By-Pass inlet/outlet
valves
2) Defective 4-way valve
or excess refrigerant
2) Readjust the quantity of refrigerant
3) Water temperature setting too high
3) Set the required temperature to 5°C above the current temperature
then proceed in increments of 5°.
4) Pressure switch disconnected or defective 4) Reconnect or replace pressure switch
5) Defective PCB 5) Replace PCB
P9
Low pressure protection
1) Insufcient refrigerant 1) Readjust the quantity of refrigerant
2) Defective 4-way valve 2) Replace valve
3) Pressure switch disconnected or defective 3) Reconnect or replace pressure switch
4) Defective PCB 4) Replace PCB
PL
Flow sensor malfunction
1) Insufcient water in heat exchanger
1) Check your water circuit operation and the opening of the By-Pass
valves
2) Defective water ow sensor 2) Replace water ow contactor
3) Defective PCB 3) Replace PCB
P6
Excessive difference between water inlet temperature and
water outlet temperature
1) Water ow rate too low
1) Check water pump and hydraulic system operation, and the opening
of the By-Pass inlet/outlet valves
2) Defective PCB 2) Replace PCB
E3
Vented air temperature too high
1) Insufcient refrigerant gas 1) Readjust the quantity of refrigerant
2) Same causes as fault E4 2) Same actions as fault E4
E6
Thermal protection
1) Water ow too low or water intake temperature
too high
1) Check water ow or adjust water temperature
2) Defective thermal protection 2) Replace protection
3) Bad connection 3) Check connections
4) Defective PCB 4) Replace PCB
E8
Problem with connection between PCB and wired remote
control
1) Bad connection
Check wiring connections between
remote control and PCB
2) Defective wired remote control 2) Replace remote control
3) Defective PCB 3) Replace PCB