PFC-4064 KEYPAD PROGRAMMING • 8870080 • REV A • 12/17
Topic Feature or
Option
Permitted
in UL
(Y/N)
Possible Settings Setting(s)
Permitted
in UL864?
Comment
Zone Zone Style Y Alarm
Supervisory
PAS
Auxiliary
Fire Drill
Waterow
System Alarm
System Supervisory
System Trouble
CO Alarm
CO Supervisory
All Settings Allowed
Zone Alarm Count Y 1-10 All Settings Allowed
Zone Silenceable Y Yes/No All Settings Allowed
Zone Silence Inhibit Y Yes/No All Settings Allowed
Zone Auto Silence Y Yes/No All Settings Allowed
Zone Auto Unsilence Y Yes/No All Settings Allowed
Zone Restore Delay Y 0-300 Sec Full range allowed
Zone Latching Y Yes/No All Settings Allowed
Zone Local Y Yes/No All Settings Allowed
Zone Output Pattern Y Constant
ANSI Temp 3
March Code
Double Time
ANSI Temp 4
All Settings Allowed
IDC-6 Dry Contact Input
Functions
Y Pull Station
Water Flow
Supervisory
Tamper
Fire Drill
Trouble Monitor
Aux
Abort
Release Follower
Reset
Silence
Fire Alarm
Disable Inputs
Disable Outputs
Disable Inputs and Outputs
Lamp Test
CO Alarm
CO Supervisory
HVAC Reset
All Settings Allowed
Exception: Disabled
functions allowed when
used with a keyed
switch.
Applies to all
dry-contact input
devices & circuits