PFC-4064 KEYPAD PROGRAMMING • 8870080 • REV A • 12/17
Topic Feature or
Option
Permitted
in UL
(Y/N)
Possible Settings Setting(s)
Permitted
in UL864?
Comment
NACs Function Y General Purpose
AMSECO Sync
Gentex Sync
Gentex Sync with T4
System Sensor Sync
Wheelock Sync
Constant Output
Resettable Output
Door Holder Output
ANSII Output
City Tie Output
All Settings Allowed
Except: A Supervisory
event cannot trigger a
T4 NAC.
Species use of
NAC circuit(s)
AUX PWR Function Y Constant Output
Resettable Output
Door Holder Output
ANSII Output
All Settings Allowed
DACT Daily Test Call Y Any time of day All Settings Allowed Alternates between
line 1 and 2 if
line 2 is enabled.
E-Mail Email Status
Reports
N Alarms, Troubles,
Supervisory, Test, History
& Status Reports
IP-Reporting IP Based Central
Station Reporting
Y Alarm, Supervisory,
Trouble & Test Reports
All Settings Allowed
On-Board
Programmable
Relays
Function Y Alarm, Supervisory,
Trouble, Low AC &
Waterow
All Settings Allowed Species use of
programmable
relays 1-4
8