Programming
120-393 632.4 04.08 Fh
PARAMOUNT two 30 - 115 kW 49
no. 6110) an the temperature difference, by which the room tem-
perature will be lowered.
Floor curing function
(850, 1150)
The floor curing function serves controlled drying out of screed
floors
Off: the function is switched off.
Functinal heating (Fh): Part 1 of the temperature profile will be
run through automatically.
Curing heating (Ch): Part 2 of the temperature profile will be run
through automatically.
Functional/curing heating: The whole temperature profile will be
run through automatically.
Manually: Control to the Floor curing setpoint manually.
Duration of the quick setback for setback by 2°C in hrs:
Outside temperature mixed:
Time constant building (Configuration, prog. no. 6110)
0 hrs 2 hrs 5 hrs 10 hrs 15 hrs 20 hrs 50 hrs
15°C 0 3,1 7,7 15,3 23
10°C 0 1,3 3,3 6,7 10 13,4
5°C 0 0,9 2,1 4,3 6,4 8,6 21,5
0°C 0 0,6 1,6 3,2 4.7 6,3 15,8
-5°C 0 0,5 1,3 2,5 3,8 5.0 12,5
-10°C 0 0,4 1,0 2,1 3,1 4,1 10,3
-15°C 0 0,4 0,9 1.8 2,6 3,5 8,8
- 20 °C 0 0,3 0,8 1,5 2,3 3,1 7,7
Duration of quick setback for setback by 4°C in hrs:
Outside temperature mixed:
Time constant building (Configuration, prog. no. 6110)
0 hrs 2 hrs 5 hrs 10 hrs 15 hrs 20 hrs 50 hrs
15°C 0 9,7 24,1
10°C 0 3,1 7,7 15,3 23,0
5°C 0 1,9 4.7 9,3 14,0 18,6
0°C 0 1,3 3,3 6,7 10,0 13,4
-5°C 0 1,0 2,6 5,2 7,8 10,5 26,2
-10°C 0 0,9 2,1 4,3 6,4 8,6 21,5
-15°C 0 0,7 1.8 3,6 5,5 7,3 18,2
- 20 °C 0 0,6 1,6 3,2 4.7 6,3 15,8