POWER ELECTRONICS
NB 120
SAFETY INSTRUCTIONS
13
The following table shows the protection class type, depending on the working voltage.
ELECTRICAL INSULATED GLOVES
Class
AC (V
AC
)
DC (V
DC
)
00
500
750
0
1000
1500
1
7500
11250
2
17000
25500
3
26500
39750
4
36000
54000
ELECTRICAL SAFETY MATTING
Class
AC (V
AC
)
DC (V
DC
)
0
1000
1500
1
7500
11250
2
17000
25500
3
26500
39750
4
36000
54000
NOTICE
PPE should be checked according to the manufacturer's instructions.
The electrical gloves must have thermal, electric and mechanical protection. Some models of gloves have
the three kinds of protection, so it is not necessary to combine them with more gloves.
If the gloves only have dielectric protection, it is mandatory to use under fireproof gloves and over gloves
cover.